DC cable voltage drop, explained.

Why both leads count, how temperature changes resistance, and what voltage drop does not tell you about safety.

Updated 24 October 2026 · Calculator v1.1.0, formula v1.0.0

Short answer: voltage drop = current × the resistance of the whole loop—the positive lead and the return lead. Resistance rises with conductor temperature, so a warm cable loses more. A low voltage drop does not prove a cable is safe: ampacity and protection are separate checks.

The formula

Loop resistance  R = 2 × L × r / 1000 × (1 + 0.00393 × (T − 20))
Voltage drop     V = I × R
Drop (%)         = 100 × V / minimum inverter-terminal voltage
Heat in cable    P = I² × R   (peak, at that current)

L is the one-way length in metres, r the conductor resistance in Ω/km at 20 °C from the cable’s datasheet, T the assumed conductor temperature in °C and I the current in amps. Example: 10 A through 1 m leads of 1 Ω/km at 20 °C gives R = 0.002 Ω, a 0.02 V drop (0.20% of 10 V) and 0.2 W of heat.

Length matters—both ways

12V class, 1000 W inverter load (100.1 A), 0.5 Ω/km at 20 °C, 75 °C conductor, 2.5% target:

One-way lengthVoltage dropDropAgainst 2.5%
1 m0.12 V1.09%Within
2 m0.24 V2.17%Within
3 m0.37 V3.26%Above
5 m0.61 V5.43%Above
8 m0.97 V8.70%Above

Keeping the battery close to the inverter is often the cheapest improvement. Every crimp, busbar, switch and fuse adds resistance too; this model counts only the cable.

What voltage drop does not tell you

  • Ampacity. Whether a conductor can carry the current safely depends on its insulation rating, installation method, bundling, ambient temperature and the applicable standard (for example NEC or ABYC). A qualified installer determines it.
  • Protection. A fuse or breaker needs a current rating, a DC voltage rating and an interrupt rating suitable for the battery’s fault current. These are separate properties.
  • Heat over a day. The heat figure is a peak at full load. Multiplying it by 24 hours assumes the load never stops and can double-count losses.

Choosing a target

Many designers aim for a few percent of drop on main battery-to-inverter cables because inverters shut down at low voltage and losses become heat. Pick a target with your installer and check it in the calculator; enter the length in feet or metres and the cable’s datasheet resistance.

Hardware to compare

Sponsored links. As an Amazon Associate BatteryCaliber earns from qualifying purchases. These open Amazon search results for each category—they are not tested, certified or endorsed products. Check every item’s manufacturer datasheet against your installer’s specification. Affiliate disclosure

Category

Class T fuses & holders

Rated current, DC voltage rating and interrupt rating are separate. Your installer must select the device and holder.

Browse on Amazon
Category

Busbars & distribution

Confirm busbar current rating, stud sizes, insulating covers and the number of connections you need.

Browse on Amazon
Category

Tinned copper battery cable

Use the cable’s datasheet resistance in the calculator. Size is set by ampacity and installation conditions, not voltage drop alone.

Browse on Amazon
Category

Crimpers & lugs

Lugs must match the conductor and stud size; follow the lug maker’s crimp tool and die specification.

Browse on Amazon

Next: 12V vs 24V vs 48V · Safety checklist